Analysis of the Contact Resistance of the 150 kV Vacuum Circuit Breaker at the Cigereleng Bay Line Lagadar Substation
DOI:
https://doi.org/10.33387/protk.v12i3.10451Keywords:
Circuit BreakerAbstract
Power Circuit Breaker (PMT) is an electrical device used to connect or disconnect the flow of electricity at medium to high voltage. The purpose of this research is to evaluate the operational feasibility condition of the PMT Vacuum Circuit Breaker 150 kV installed on the Lagadar bay line. To what extent the device still meets the technical requirements according to the applicable standards, technical testing is conducted to determine the extent to which the PMT Vacuum Circuit Breaker 150 kV still meets the technical requirements according to the applicable standards. The methods used include insulation resistance testing, contact resistance testing, and contact bounce testing. This research was conducted by comparing the test results obtained with the standards. The contact resistance test yielded the following values phase R at 37 μΩ, phase S at 34 μΩ, and phase T at 40 μΩ, all of which are below the maximum threshold of 50 μΩ according to IEC 60694 standards. Meanwhile, in the contact synchronization test, the closing times were: phase R 74.60 ms, phase S 71.15 ms, and phase T 72.05 ms, and the opening times were: phase R 24.65 ms, phase S 30.80 ms, and phase T 24.70 ms. The time differences between phases are still within the acceptable synchronization limits (below 10 ms).
Downloads
References
Adis Galih Firdaus, R. H. (2021). Analisa Pengujian Kelayakan Operasi Pemutus Tenaga (PMT) 150 kV Bay Penghantar Mandirancan I Berdasarkan Parameter Breaker Analyzer di Gardu Induk Sunyaragi. ELECTRICIAN – Jurnal Rekayasa dan Teknologi Elektro, 253.
Cheng, T. G. (2018). valuation method of contact erosion for high voltage SF6circuit breakers using dynamic contact resistance measurement. Electric Power Systems Research 163., 725-732.
deden Emil Salam, E. M. (2021). Analisis Uji Kelayakan PMT Pada Jaringan Tenaga LISTRIK 150 KV. Jurnal Kehumasan P-ISSN:, 4(2), 1–9.
Díaz, S. N. (2020). Study of technologies implemented in the operation of SF6 switches. InIOP Conference Series: Materials Science and Engineering(Vol. 872, No. 1, p. 012041). IOP Publishing.
Feiming, W. B. (2017). Test analysis of dielectric recovery characteristic in high voltage SF6circuit breaker. In 2017 4th International Conference on Electric Power Equipment-Switching Technology (ICEPE-ST), 11-15.
Firdaus, M. Y. (2023). ANALISIS HASIL PENGUKURAN TAHANAN ISOLASI PADA PEMUTUS TENAGA (PMT) KUBIKEL 20 KV DI GARDU INDUK JENEPONTO. Jurnal MEDIA ELEKTRIK, Vol. 20, No. 2, 148.
Guo, Z. L. (2022). SF6 High-Voltage Circuit Breaker Contact Status Detection at Different Currents. Sensors, 22(21), 8490.
MOCHAMMAD SYACHBANI IRAWAN, T. A. (2023). Analisis Kinerja Pemutus Tenaga pada Gardu Induk 6,3 kV di PT Indonesia Power Kamojang. Prosiding Seminar Nasional Energi, Telekomunikasi dan Otomasi SNETO 2023, 117 .
Muhammad Mursal Fikri, I. A. ( 2021). Pengujian Tahanan Kontak Pemutus Tenaga 70 KV Di Gardu Induk Rengas Dengklok Karawang. JE-UNISLA Electronic Control, Telecomunication, Computer Information and Power Systems Volume 6 No 2 , 7-8.
Prakoso, M. A. (2024). Analisis Pengujian dan Pemeliharaan Dua Tahunan Pemutus Tenaga (PMT) Di Gardu Induk Rungkut 150 kV. Jurnal Teknik Elektro, Volume 13 Nomor 2, 144-151.
Rezza Badruzzaman, A. S. (2021). Analysis of Contact Resistance Test PMT Bay Kuningan II 70KV at Sunyaragi Substation. Journal of Electrical and Electronic Engineering-UMSIDA ISSN 2460-9250 (print), ISSN 2540-8658 (online) Vol. 5, No. 2, , 116-138.
Rizky Fiqliyarli Rezyan, A. S. (2024). KELAYAKAN PEMUTUS TENAGA 150 KV BERDASARKAN UJI TAHANAN ISOLASI DAN TAHANAN KONTAK. EPIC (Journal of Electrical Power, Instrumentation and Control) Teknik Elektro – Universitas Pamulang Vol. 7, No. 1, 46.
Saghawari, A. A. (2019). Analisa Kinerja Circuit Breaker Saat Gangguan Pada Sisi 70 KV Di Gardu Induk Teling. Repository Universitas Sam Ratulangi , hal. 1-8.
Vianna, E. A. (2017). Substations SF6circuit breakers: Reliability evaluation based on equipment condition. Electric Power Systems Research, 36-46.
Wiharja, U. (2019). Analisa Pengujian Transformator 2 MVA. . Jurnal Elektrokrisna Vol. 7 No. 2, 57-67.
Downloads
Additional Files
Published
How to Cite
Issue
Section
License
Copyright & License
Copyright, licensing, and reuse terms for articles published in Protek: Jurnal Ilmiah Teknik Elektro
1. Copyright
Authors who publish in Protek: Jurnal Ilmiah Teknik Elektro retain the copyright of their work. Copyright of each article is vested exclusively in its authors.
2. License
Articles in Protek are published under the Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License (CC BY-NC-SA 4.0). Anyone may share and adapt the work under the following terms:
3. Author's Warranties
By submitting a manuscript, the author warrants that the article:
- is original and has not been published before;
- contains no unlawful statements;
- does not infringe the rights of others;
- is subject to copyright vested exclusively in the author(s); and
- includes any necessary permissions to quote material from other sources.
4. User Rights
Under CC BY-NC-SA 4.0, users may copy, distribute, display, and perform the work for non-commercial purposes only. When distributing the work, users must give proper credit to the authors and to Protek as the original place of publication.
7. Royalties
The parties agree that no royalties or other fees are paid to the authors for publication. To the extent legally permissible, authors waive any claim to royalties for the publication of their article.
8. Miscellaneous
- Protek publishes the article in electronic form and makes it freely available to the public, without charge to readers.
- The editors may modify the article to conform to the journal's style, including punctuation, spelling, capitalization, referencing, and usage.
Questions about copyright or licensing can be sent to protek@unkhair.ac.id. See also the Open Access Policy and Publication Ethics.