Analisis Kualitas Minyak Trafo Menggunakan Data Dissolved Gas Analysis dan Water Content
DOI:
https://doi.org/10.33387/protk.v5i1.262Keywords:
Dissolved Gas Analysis, Oil Transfomer, Water Content, Rasio Roger, Duval Triangle.Abstract
Transformer is a vital equipment in the power system. If the transformer is damage, can cause the electrical distribution to the consumer will be disrupted. Therefore, it needs special maintenance the performance of the transformer to avoid damage. One of them is the maintenance of the transformer oil. During the operation, the transformer oil will experience about thermal and electrical loading. Due to the load can cause dissolved gases in oil that could potentially lead to a breakdown in the transformer. It is needed monitoring against these gases. The other way to analyze the gas dissolved in oil is by using Dissolved Gas Analysis (DGA) test. The DGA will extract gases to know indications based on the interpretation of the data were performed. Therefore, damage of the transformer can be prevented. The results of DGA analysis on the transformer were discharge of energy and thermal fault obtained from data interpretation using Ratio Roger and Duval Triangle method. Also, it can be known that, the results of water content testing indicate oil condition are good (water content < 9 ppm).
Keywordsâ€â€Dissolved Gas Analysis, Oil Transfomer, Water Content, Rasio Roger, Duval Triangle.
References
Buku Pedoman Pemeliharaan Transformator Tenaga, No. PDM/PGI/01, Jakarta Selatan, Indonesia: Dokumen PT PLN (Persero). 2014.
Rahmatullah Arif F, M, “Analisis Indikasi Kegagalan Transformator dengan Metode Dissolved Gas Analysâ€Â, Tugas Akhir Teknik Elektro, FT UNDIP, Semarang, 2011.
Pedoman penerapan spesifikasi dan pemeliharaan minyak isolasi. SPLN 49-1.1982.
G. I. M. Setiawan, I. Garniwa, “Analisis kondisi minyak transformator berdasarkan uji parameterâ€Â, Skripsi, Jurusan Teknik Elektro, Universitas Indonesia, Jakarta, 2013.
Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers,IEEE Std C57.104-2008, 2008.
IEC 60599, “Mineral oil-impregnated electrical equipment in service : Guide to the interpretation of dissolved and free gases analysisâ€Â, IEC Publication 60599 (1999-2003), Mar.1999.
IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment,IEEE Std C57.106-2006, 2006.
Iryanto, Irwan. 2011. “Analisis Gas Terlarut Pada Minyak Isolasi Akibat Pembebanan dan Penuaanâ€Â. TEKNIK. Volume 32, No.3.
Mahardika, Agra. 2017. “Perbaikan Parameter DIELEKTRIK (Tegangan Tembus, TAN Ά, Resistivitas Dan Water Content) Minyak Isolasi Transformator Dengan Metode Purifikasi (Boiling) Pada Suhu 26℃-100OCâ€Â. TRANSIENT.Volume 6, No.2.
Wibowo, Wahyu Kunto. 2008. â€ÂAnalisis Karakteristik Breakdown Voltage Pada Dielektrik Minyak Shell Diala B Pada Suhu 30℃-1300℃â€Â. E-prits Undip.
Published
How to Cite
Issue
Section
License
Authors who publish with this journal agree to the following terms:
- The copyright of the accepted for publication articles shall be assigned to Protek : Jurnal Ilmiah Teknik Elektro as the publisher of the journal. The intended copyright includes the rights to publish articles in various forms (including reprints).
- Protek : Jurnal Ilmiah Teknik Elektro maintain the publishing rights of the published articles.
- Authors are permitted to republish or disseminate published articles by sharing the link/DOI of the article at Protek : Jurnal Ilmiah Teknik Elektro. Authors are allowed to use their articles for any legal purposes deemed necessary without written permission from Protek : Jurnal Ilmiah Teknik Elektro with an acknowledgment of initial publication to this journal.
Protek : Jurnal Ilmiah Teknik Elektro by Department of Electrical Engineering, Faculty of Engineering, Universitas Khairun
This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.