Impact of Reactive Power Fluctuation on the Performance and Insulation Loss-of-Life Rate of Industrial Power Transformers: A Case Study of the PT Semen Tonasa Electrical System

Penulis

  • Muh. Imran Bachtiar Politeknik Negeri Ujung Pandang
  • Aksan Politeknik Negeri Ujung Pandang
  • Rahmat Budiansa Politeknik Negeri Ujung Pandang

DOI:

https://doi.org/10.33387/protk.v13i2.12746

Kata Kunci:

ETAP, insulation ageing rate power factor, power transformer

Abstrak

Power transformer performance is strongly influenced by reactive power (VAR), yet the quantitative link between VAR fluctuation and insulation loss-of-life in heavy industrial systems remains under-documented. This study analyzes that link for six 70 kV power transformers (three at the Tonasa IV and three at the Tonasa V substations, 31.5–40 MVA) in the electrical system of PT Semen Tonasa, combining SCADA operational data, an ETAP load-flow simulation, and an analytical ageing-rate calculation based on IEC 60076-7. Varying reactive power from 1 to 10 MVAR at a fixed active power of 10 MW increased the loading level from 31.41% to 44.19% of the 80% operating limit, consistent with S = √(P²+Q²). SCADA records showed current rising and primary-side voltage falling as VAR increased, with all voltages (66.68–68.95 kV) remaining within ±10% of nominal. For the three Tonasa V units, hotspot temperatures of 65.42–75.23°C and loss-of-life rates of 0.022–0.069 pu/day were obtained, well below the 98°C/V = 1 design reference; Transformer #1 aged roughly 3.1 times faster than Transformer #2, reflecting its higher average loading (63.4% vs. 36.5% of the operating limit). The extrapolated remaining-life figures (79.7–250 years) are indicative rather than literal, given the short (3–5-day) SCADA window; the loss-of-life rate is therefore treated as the primary, more defensible indicator. Reactive-power compensation via capacitor banks or static var compensators is recommended to limit current, hotspot temperature, and insulation ageing.

Unduhan

Data unduhan belum tersedia.

Biografi Penulis

Muh. Imran Bachtiar, Politeknik Negeri Ujung Pandang

Muh. Imran Bachtiar is a lecturer in the Department of Electrical Engineering, Bachelor of Applied Science (D4) in Electrical Engineering Study Program at Politeknik Negeri Ujung Pandang, Indonesia. He currently holds the academic position of Asisten Ahli with the civil service rank of Penata Muda Tingkat I (Grade III/b).

Referensi

[1] J. Wang, X. Zhang, F. Zhang, J. Wan, L. Kou, and W. Ke, “Review on Evolution of Intelligent Algorithms for Transformer Condition Assessment,” Frontiers in Energy Research, vol. 10, p. 904109, 2022, doi: 10.3389/fenrg.2022.904109.

[2] H. Dirik, C. Gezegin, and H. S. Dirik, “Reactive Power Compensation with Hybrid Compensator Combining a Synchronous Motor and Switched Capacitors,” Electric Power Systems Research, vol. 216, p. 109010, 2023, doi: 10.1016/j.epsr.2022.109010.

[3] T.-D. Nguyen, A.-T. Bui, N.-K. Nguyen, T.-D. Bui, N.-Q. Dinh, and T.-D. Pham, “A Novel Hybrid DC–CC-Based Reactive Power Compensation Scheme to Improve Power Quality of an Electric Grid Considering the Efficiency of Asynchronous Induction Motors,” SSRG International Journal of Electrical and Electronics Engineering, vol. 10, no. 8, pp. 156–169, 2023, doi: 10.14445/23488379/IJEEE-V10I8P115.

[4] M. Ayaz, S. M. H. Rizvi, and M. Akbar, “Dynamic Power Factor Correction in Industrial Systems: An Automated Capacitor Bank Control Approach,” in 2023 2nd International Conference on Emerging Trends in Electrical, Control, and Telecommunication Engineering (ETECTE), 2023, pp. 1–6, doi: 10.1109/ETECTE59617.2023.10396685.

[5] S. Bilyaz, A. Bhati, M. Hamalian, K. Maynor, T. Soori, A. Gattozzi, C. Penney, D. Weeks, Y. Xu, L. Hu, J. Y. Zhu, J. K. Nelson, R. Hebner, and V. Bahadur, “Modeling the Impact of High Thermal Conductivity Paper on the Performance and Life of Power Transformers,” Heliyon, vol. 10, no. 6, p. e27783, 2024, doi: 10.1016/j.heliyon.2024.e27783.

[6] G. Kosobudzki, D. Dusza, M. P. Ciurys, and A. Leicht, “Reactive Power Compensation for Single-Phase AC Motors Using Integral Power Theory,” Energies, vol. 18, no. 10, p. 2641, 2025, doi: 10.3390/en18102641.

[7] M. A. Fahmi, E. Radwitya, and Hasan, “Rancang Bangun Kapasitor Bank Otomatis Berbasis Internet of Things (IoT) pada Rumah Tinggal,” Electrical Network Systems and Sources, vol. 3, no. 2, pp. 6–13, 2024, doi: 10.58466/entries.v3i2.1608.

[8] B. Rezaeealam, “Real-Time Monitoring of Transformer Hot-Spot Temperature Based on Nameplate Data,” IET Generation, Transmission & Distribution, vol. 17, no. 12, pp. 2789–2801, 2023, doi: 10.1049/gtd2.12884.

[9] A. Anca, B. Bakhtiar, and R. L, “Study of the Effect of Peak Load on Transformer Loss of Life at PT PLN (Persero) Rayon Daya,” Jurnal Teknologi Elekterika, vol. 16, no. 2, pp. 80–87, 2019, doi: 10.31963/elekterika.v16i2.1550.

[10] International Electrotechnical Commission, IEC 60076-7:2018 Power Transformers – Part 7: Loading Guide for Mineral-Oil-Immersed Power Transformers, Geneva: IEC, 2018.

[11] IEEE Std C57.91-2011, IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators, Piscataway, NJ: IEEE, 2012.

[12] K. Kumar, B. G. Kumbhar, and S. Satsangi, “Assessment of Effect of Load Models on Loss-of-Life Calculation of a Transformer Using a Point Estimation Method,” Electric Power Components and Systems, vol. 46, no. 16–17, pp. 1808–1819, 2018, doi: 10.1080/15325008.2018.1511874.

[13] J. Lu, B. Brown, Q. Hong, C. Booth, and B. Stephen, “Impact of Reactive Power Assumptions on Physics-Informed Assessment of Transformer Ageing in Distribution Networks,” PHM Society European Conference, vol. 9, no. 1, pp. 1–9, 2026, doi: 10.36001/phme.2026.v9i1.5031.

[14] S. A. Giha Yidi, V. Sousa Santos, K. Berdugo Sarmiento, J. E. Candelo-Becerra, and J. de la Cruz, “Comparison of Reactive Power Compensation Methods in an Industrial Electrical System with Power Quality Problems,” Electricity, vol. 5, no. 3, pp. 642–661, 2024, doi: 10.3390/electricity5030032.

[15] R. S. Juwita and Liliana, “Forecasting Analysis of Power Transformer Loss of Life Based on Loading Using the Linear Regression Method,” Briliant: Jurnal Riset dan Konseptual, vol. 8, no. 3, pp. 723–730, 2023, doi: 10.28926/briliant.v8i3.1286.

[16] A. Pavlićević and S. Mujović, “Impact of Reactive Power from Public Electric Vehicle Stations on Transformer Aging and Active Energy Losses,” Energies, vol. 15, no. 19, p. 7085, 2022, doi: 10.3390/en15197085.

[17] L. R. Chandran, G. S. Ajith Babu, M. G. Nair, and K. Ilango, “A Review on Status Monitoring Techniques of Transformer and a Case Study on Loss of Life Calculation of Distribution Transformers,” Materials Today: Proceedings, vol. 46, pp. 4659–4666, 2021.

[18] N. Rosyidi A. S., G. Andika, E. Supriyadi, and Ariman, “Analysis of the Life Reduction of a 1250 kVA Transformer Due to Loading at a Private Hospital Transformer,” Sainstech, vol. 34, no. 1, pp. 52–63, 2024, doi: 10.37277/stch.v34i1.1997.

[19] A. Maruf and Y. Primadiyono, “Analysis of the Effect of Loading and Temperature on the Loss of Life of 60 MVA Power Transformer Units 1 and 2 at the 150 kV Kalisari Substation,” Edu Elektrika Journal, vol. 10, no. 1, pp. 1–10, 2021.

[20] K. M. Berdugo Sarmiento, J. I. Silva-Ortega, V. Sousa Santos, J. E. Candelo-Becerra, and F. E. Hoyos, “Improving the Operation of Transmission Systems Based on Static Var Compensator,” Electricity, vol. 6, no. 3, p. 40, 2025, doi: 10.3390/electricity6030040.

Diterbitkan

2026-10-28

Cara Mengutip

Bachtiar, M. I., Aksan, & Budiansa, R. (2026). Impact of Reactive Power Fluctuation on the Performance and Insulation Loss-of-Life Rate of Industrial Power Transformers: A Case Study of the PT Semen Tonasa Electrical System. PROtek : Jurnal Ilmiah Teknik Elektro, 13(2), 147–154. https://doi.org/10.33387/protk.v13i2.12746